Raman Optical Fiber Distributed Temperature Sensor
Part Code: DTSenz
- Temperature Measurement Range : -40°C to 150°C
- Predictive maintenance of valuable assets.
- Cost efficient tool on operating over entire life cycle.
- Quick detection and exact location of fire event.
- Reliable measurements over long distances
A Distributed Temperature Sensing (DTS) system is ideal for fire detection and monitoring long-distance temperature profiles. DTS is a linear system capable of detecting temperature over the entire length of an optical fiber cable.
When a light source (laser) propagates down an optical fiber, it exchanges molecules with lattice vibration. On application of heat, it is scattered back by the glass fiber molecules to the transmitted end where it is analyzed. Nearly all the scattered light has a wavelength identical to incident light, small amount of light has a different wavelength due to Raman Effect. On Raman scattering, stokes and anti-stokes signals generate, the intensity ratio of which is dependent on temperature. The arrival time of backscattered signals is used to determine the position of temperature readings, a principle known as Optical Time Domain Reflectometry (OTDR).
Applications
- Linear temperature sensing along pipelines and tunnels.
- Fire detection inside tunnels.
- Oil and gas leakage along pipelines.
- Conveyor Belt Monitoring.
- Reactor Skin Temperature Monitoring.
Technical Datasheet
Temperature Measurement Range | -20 to 120°C standard cable |
Temperature Accuracy | ±2°C @ 10 km,6s |
Temperature Resolution | 0.1°C |
Sensing Range | 10 Km, 25 km |
Sampling Resolution | 0.4 m |
Spatial Resolution | 2 m |
Position Accuracy | ±1 m |
Number of Channels | 1/2/4/8/16 |
Temperature Unit | °C or °F |
Measurement Time | 1 Second Per Channel |
Communication Ports | RS-485, Ethernet (RJ-45) |
Communication Protocol | MODBUS, TCP/IP |
Sensing Fiber | Single Mode and Multimode Fiber |
Relative Humidity | 5 to 90% |
Power Supply | 100 – 230 V AC, 50 – 60 Hz |
Power Consumption | 15 Watt |
Working Temperature | -10 to +50°C |
Storage Temperature | -40 to +70°C |
- Thousands of sensing points available on single channel; max upto four channels.
- Sensor cable length: Upto 10 Km.
- Communication interface: RJ45, RS485.
- Optical fiber is robust, chemically inert and intrinsically safe for operation.
- Proven DTSenz fiber optic cable; Suitable for monitoring large linear assets, such as tunnels, oil & gas pipelines, nuclear power plant, and conveyer belts.